Room/Indoor Temperature Transmitter

Room/Indoor Temperature Transmitter
Product Detailed
Related Categories:Temperature Instruments
Room temperature transmitter Indoor temperature measurement. 0-10V or 4-20mA measuring signals

Features    

·          Indoor temperature measurement.

·          Simple and secure installation

·          Wide range of temperature probes

·          010V or 420mA measuring signals

·          Compact size and modern design

Applications

·          Indoor air temperature measurement for comfort control

·          Frost protection sensor

Temperature Tansmitter

The room temperature transmitter measures the temperature by the use of a PT1000 sensing element. The transmitter analog output may be be 0-10V or 4-20mA. And the transmitter include a noise filter.the power suply is large range VDC18V----VDC30V.Standard temperature measurment range is -3070 °C.

  Ordering

Ordering number:TS-U/I-R

-U indicates the transmitter singal out is 0-10V.

-I  indicates the transmitter signal out is 4-20mA.

For example:TS-U-R

The duct temperature transmitter signal out is 0-10V.

Installation

Mount the temperature sensor on a flat interior wall of the room to be controlled. Do avoid obstructions such as shelves, curtains and recesses. Do not place near heat sources, draft channels. Do not expose to direct sunlight.

·          When installing the unit, fix the base plate first, connect the electrical connections then hook on the cover and secure it.

·          The end of the conduit at the sensor must be sealed to prevent false measurements due to draughts through the conduit.

·          Connect the wires according to the wiring diagram to the measuring circuit in the cover:

o         If the transmitter signal out is 0-10V,its need three terminal connections,DC24V,Ground and signal out.

o         If the transmitter signal out is 4-20mA,its need two terminal connections,DC24V,Ground and signal out.

o         The connection signal cable should be shield wires.

Technical Specification

Power suply

Option voltage

VDC18V---VDC30V

Power Cunsumption

Max 2 VA

Signal outputs

-U type

0-10VDC

-I  type

4-20mA

accuracy

0.5%

Temperature range

-30-----70°C

Sensing elements

Platinum-Film:

Range

Accuracy

PT,  0.3851ohm/k

-30----70°C

±0.3k

Connection

Connection Terminals

2.5 mm2

Environment

OperationClimatic ConditionsTemperatureHumidity

To IEC 721-3-3class 3 K5-4070°C<95% r.h.

Transport & StorageClimatic ConditionsTemperatureHumidityMechanical Conditions

To IEC 721-3-2 and IEC 721-3-1class 3 K3 and class 1 K3-4080°C<95% r.h.class 2M2

Standards

          conform according to EMC Standard 89/336/EECEMEI Standard 73/23/EEC

EN 61 000-6-1/ EN 61 000-6-3

Automatic electrical controls for household and similar use

Special requirement on temperature dependent controls

EN 60 730 1

EN 60 730 2 - 9

Pollution Class

Normal acc. To EN 60 730,RoHS compliant

Degree of Protection

IP56 to EN 60 529

Safety Class

III (IEC 60536)

Housing Materials

       Cover & Mounting Plate

Fire proof ABS plastic

General

Dimensions [mm]

Cover: 42 x 112 x 88 (H x W x D)

Weight (including package)

135g

Room/Indoor Temperature Transmitter



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.